Skip to main content
Wybierz kraj / język

nVent ERIFLEX Power Meters and Software Najedź kursorem, aby powiększyć obraz, lub kliknij, aby go powiększyć.

nVent ERIFLEX Power Meters & Software

The nVent ERIFLEX Network Analyzer is a compact and innovative instrument designed for precise measurement and recording of electrical parameters. It is particularly well-suited for energy consumption analysis and control.

Its quick and easy connection system makes it ideal for retrofitting existing switchboards or conducting energy audits. The analyzer is the perfect tool for establishing measurement points across a facility.

Communication is supported via an RS485 serial port using MODBUS RTU protocol (PM RS485 version) and an Ethernet port using MODBUS TCP protocol (PM Ethernet version).

Remote management is available through the free EriflexNET software. For Ethernet models, an integrated web interface allows full access and control from any PC connected to the network, offering a convenient and intuitive way to manage the device remotely. You can download the EriflexNET software from the Resources tab below.

Czytaj dalej Wyświetl mniej
  • RoHS
  • CE
Wydrukuj tę stronę
Potrzebujesz pomocy technicznej lub wyceny? Z chęcią pomożemy.
Kontakt Gdzie kupić
Szczegóły

Funkcje

Specyfikacje

Wycięcie montażowe 3.58x3.58"
Częstotliwość 45 - 65 Hz
Wycięcie montażowe 91x91mm
Aktualny zakres pomiaru 500 A; 4000 A; 20000 A
Napięcie wejściowe 600 VAC
Zgodność z 2014/30/EU;2014/35/EU;EN 61010-1;EN 61010-2-030
Dokładność częstotliwości ±0,1% odczytu ±1 cyfra w zakresie 45–65 Hz
Dokładność napięcia ±0,2% odczytu w zakresie od 10% FS do FS
Dokładność pomiaru prądu ±0,4% odczytu w zakresie od 5% FS do FS
Temperatura pracy -13 to 131 °F
Temperatura przechowywania -13 to 167 °F
Temperatura pracy -25 to 55 °C
Temperatura przechowywania -25 to 75 °C
Wilgotność 80 % Max
Instalacja Wewnątrz
Ocena IP IP54;IP20
Skopiowane dane
Metryczne   |   Imperialne
PMETHERNET PMRS485
Minimum voltage for FFT calculation 20/35 VAC (direct connection; multiplied by PT ratio when using PT)
Starting current (Ist) 3A for FSA 500A
25A for FSA 4000A
120A for FSA 20000A
Current Inputs Rogowski coil inputs
(3 coils, ordered separately)
Wiring Modes Compatible with both single-phase and three-phase systems
Active power/energy accuracy Class 0.5 per IEC/EN 61557-12
Reactive power/energy accuracy Class 2 per IEC/EN 61557-12
Digital Outputs Type: 2 x NPN, Passive Optoisolated
Max Values: 27 VDC - 27 mA
Digital Inputs Type: Optoisolated
Voltage Range: 80 - 265 VAC-DC
Terminal wire diameters Measuring Terminals: 2.5 mm2 / 14 AWG
I/O, AUX, RS485 terminals: 1.5 mm2 / 16 AWG

Schematy

Ilustracje przedstawiające zastosowania Zasoby
Ostrzeżenie
Produkty nVent powinny być instalowane i używane wyłącznie zgodnie z instrukcjami i materiałami szkoleniowymi nVent. Instrukcje są dostępne na stronie www.nvent.com oraz u przedstawiciela działu obsługi klienta firmy nVent. Nieprawidłowa instalacja, niewłaściwe użycie, niewłaściwe zastosowanie lub inne nieprzestrzeganie instrukcji i ostrzeżeń nVent może spowodować nieprawidłowe działanie produktu, uszkodzenie mienia, poważne obrażenia ciała i śmierć i/lub utratę gwarancji.
Potrzebujesz pomocy technicznej lub wyceny? Z chęcią pomożemy.
Kontakt Gdzie kupić