The nVent ERIFLEX Network Analyzer is a compact and innovative instrument designed for precise measurement and recording of electrical parameters. It is particularly well-suited for energy consumption analysis and control.

Its quick and easy connection system makes it ideal for retrofitting existing switchboards or conducting energy audits. The analyzer is the perfect tool for establishing measurement points across a facility.

Communication is supported via an RS485 serial port using MODBUS RTU protocol (PM RS485 version) and an Ethernet port using MODBUS TCP protocol (PM Ethernet version).

Remote management is available through the free EriflexNET software. For Ethernet models, an integrated web interface allows full access and control from any PC connected to the network, offering a convenient and intuitive way to manage the device remotely. You can download the EriflexNET software from the Resources tab below.

Läs mer Läs mindre
  • RoHS
  • CE
Skriv ut den här sidan
Need technical support or a quote? We're here to help.
Contact Us Where to Buy
Information

Design

Specifikationer

Utskärning av montering 3.58x3.58"
Frekvens 45 - 65 Hz
Utskärning av montering 91x91mm
Aktuellt mätområde 500 A; 4000 A; 20000 A
Inspänning 600 VAC
Överensstämmer med. 2014/30/EU;2014/35/EU;EN 61010-1;EN 61010-2-030
Noggrannhet för frekvens ±0,1 % av mätvärdet ±1 siffra inom intervallet 45–65 Hz
Noggrannhet för spänning ±0,2 % av mätvärdet inom 10 % FS till FS-intervallet
Noggrannhet för strömmätning ±0,4 % av mätvärdet inom 5 % FS till FS-intervallet
Drifttemperatur -13 to 131 °F
Förvaringstemperatur -13 to 167 °F
Drifttemperatur -25 to 55 °C
Förvaringstemperatur -25 to 75 °C
Luftfuktighet 80 % Max
Installation Inomhus
IP-klassning IP54;IP20
Data kopierades
Metrisk   |   Imperiala
PMETHERNET PMRS485
Minimum voltage for FFT calculation 20/35 VAC (direct connection; multiplied by PT ratio when using PT)
Starting current (Ist) 3A for FSA 500A
25A for FSA 4000A
120A for FSA 20000A
Current Inputs Rogowski coil inputs
(3 coils, ordered separately)
Wiring Modes Compatible with both single-phase and three-phase systems
Active power/energy accuracy Class 0.5 per IEC/EN 61557-12
Reactive power/energy accuracy Class 2 per IEC/EN 61557-12
Digital Outputs Type: 2 x NPN, Passive Optoisolated
Max Values: 27 VDC - 27 mA
Digital Inputs Type: Optoisolated
Voltage Range: 80 - 265 VAC-DC
Terminal wire diameters Measuring Terminals: 2.5 mm2 / 14 AWG
I/O, AUX, RS485 terminals: 1.5 mm2 / 16 AWG

Diagrams

Tillämpningsbilder Resurser
Varning
nVent produkter ska installeras och användas endast så som anges i nVents bruksanvisning och utbildningsmaterial. Bruksanvisningar är tillgängliga på www.nvent.com och från din nVent kundtjänstrepresentant. Felaktig installation, missbruk, felapplicering eller annan brist i att helt följa nVents instruktioner och varningar kan orsaka att produkten brister, egendomsskador, allvarliga kroppsskador och dödsfall och/eller ogiltigförklara din garanti.