Features
- Flexible insulated copper-plated, aluminum flat braid
- Better current/ampacity than cable due to skin effect
- Much more flexible than cable
- No bending radius to respect
- Ready-to-use from one side with direct connection on busbar or circuit breaker palm
- Only one conductor per phase from 400kVA (560 A) to 1600kVA (2250 A) and two conductors per phase for 2000kVA (2800 A) to 3150kVA (4435 A)
Specifications
| Wire Diameter | 0.2mm |
| Insulation Thickness | 2.5 - 3.5 mm |
| Dielectric Strength | 20kV/mm |
| Nominal Voltage, IEC | 1000V;1500V |
| Max Working Voltage, EN 50264-3-1 | 6000V |
| Connector Material | Copper |
| Conductor Material | Copper Clad Aluminum |
| Complies With | IEC® 60695-2-11 (Glow Wire Test 960 °C);IEC® 61439.1;IEC® 61439.1 Class II;IEC® 60364 |
| Halogen Free Rating | UL® 2885;IEC® 60754-1;IEC® 62821-2 |
| Low Smoke Rating | IEC® 61034-2;ISO 5659-2;UL® 2885 |
| Mechanical Resistance Rating | IK09 |
| Connector Finish | Tinned |
| UV Resistance Rating | UL® 2556;UL® 854 |
| Flammability Rating | UL® 94V-0 |
| Working Temperature | -50 to 115 °C |
| Insulation Elongation | 500 % Min |
Catalog Number
1
to
25
of
172
Page
1
of
7
| Installation Standard | AS 3008;BS 7671;CEI 64-8;CSN;DIN VDE 0100;HD 384;IEC® 60364 |
| Current Coefficient According to Temperature Rise | ||||||||
| Temperature Rise | ΔT 30°C | ΔT 40°C | ΔT 45°C | ΔT 50°C | ΔT 55°C | ΔT 60°C | ΔT 65°C | ΔT 70°C |
| Derating Coefficient | 0.71 | 0.82 | 0.87 | 0.91 | 0.96 | 1.00 | 1.04 | 1.08 |
Engineering Specification
Flyer
Installation Manual / Instruction Sheet
Technical Handbook
Certifications
ERIFLEX FleXbus LSHFFR CC13323
English
IEC 61034-2; ISO 5659-2; UL 2885; IEC 60754-1; IEC 62821-2; UL 94; IEC 60695-2
IEC 61439-1 FleXbus 1X01084-06
English,French
IEC 61439-1
IEC 61439-1 ERIFLEX FleXbus Conductor 1X01084-06
English,French
IEC 61439-1 Class II
IEC 61439-1 Class II ERIFLEX FleXbus Conductor 1X01084-05
English,French
IEC 61439-1 Class II
UR, QEUY2.E125470, FleXbus Conductor
English
ANSI/UL 67, ANSI/UL 891
UKCA, ERIFLEX FleXbus
English
EN IEC 61439-1; EN IEC 60364; EN IEC 61914
FleXbus Temp. Rise
English
IEC 61439-1, IEC 60364
IEC 60695-2-12 CC13021_FADV
English
IEC 60695-2-12
CE, ERIFLEX FleXbus
English
EN IEC 61439-1; EN IEC 60364; EN IEC 61914
ERIFLEX UV CC13222_FADV
English
IEC 60364-5-52, ISO 4892-2
IEC 61439-1:2011 CL2
English
IEC 61439-1:2011






- Warning
- nVent products shall be installed and used only as indicated in nVent's product instruction sheets and training materials. Instruction sheets are available at www.nvent.com and from your nVent customer service representative. Improper installation, misuse, misapplication or other failure to completely follow nVent's instructions and warnings may cause product malfunction, property damage, serious bodily injury and death and/or void your warranty.