nVent CADDY Fire-Rated Cable Holder, Metal


nVent CADDY Fire-Rated Cable Holder, Metal
nVent CADDY Fire-Rated Cable Holder, Metal is a versatile bracket designed to support medium-sized cable bundles in crowded spaces, such as above suspended ceilings. Compatible with traditional anchoring and direct fastening for both wall and ceiling mounts, it presents a unique, tool-free closing mechanism that can be operated safely from the ground without a ladder or lift—ultimately saving contractors time on the job. Featuring a short profile design and compliance to DIN 4102-12, this cable holder is an ideal solution for electrical and datacom applications.
Podrobnosti
Obrázky aplikací
Prostředky
CAD
Video
Související produkty
Vlastnosti
- E30-E90 classification according to DIN 4102-12
- Compatible with direct fastening and traditional anchoring
- Requires only one nail per holder
- Reusable in case of nail misfire
- Unique closing mechanism which can be safely operated from the ground
- Rounded edges help prevent cable damage
- Ready to use out of the box
- Made of 100% recyclable materials
Specifikace
Povrchová úprava | Pregalvanized |
Materiál | Ocel |
E30 Fire Rating Power Cable Capacity | ||||
---|---|---|---|---|
Part Number | Mount | Fastener | Cable | kg/m** |
KLICK15 | Ceiling | X-P 17 B3 MX / X-P 20 B3 MX / Fire-rated Anchor* | BETAflam® (N)HXH-J FE180 / E30–E60 S 0,6/1kV n1 x 1,5 RE | 3 |
BETAflam® (N)HXH-J FE180 / E30–E60 S 0,6/1kV n1 x 2,5 RE | ||||
BETAflam® (N)HXH-J FE180 / E90 0,6/1kV n1 x 1,5 RE | ||||
BETAflam® (N)HXH-J FE180 / E90 0,6/1kV n2 x 2,5 RE | ||||
EUCASAFE® (N)HXH FE 180 E30 - E60 0,6/1 kV n1 x 1,5 RE | ||||
EUCASAFE® (N)HXH FE 180 E30 - E60 0,6/1 kV n1 x 2,5 RE | ||||
EUCASAFE® (N)HXH FE 180 E90 0,6/1 kV n1 x 1,5 RE | ||||
EUCASAFE® (N)HXH FE 180 E90 0,6/1 kV n3 x 2,5 RE | ||||
Keram (N)HXH-J FE180 E30-E60 0,6/1 kV n1 x 1,5 RE | ||||
Keram (N)HXH-J FE180 E30-E60 0,6/1 kV n1 x 2,5 RE | ||||
Keram (N)HXH-J FE180 E90 0,6/1 kV n2 x 1,5 RE | ||||
Keram (N)HXH-J FE180 E90 0,6/1 kV n3 x 2,5 RE | ||||
Wall | Fire-rated Anchor* | EUCASAFE® (N)HXH FE 180 E30 - E60 0,6/1 kV n1 x 1,5 RE | 3 | |
EUCASAFE® (N)HXH FE 180 E30 - E60 0,6/1 kV n1 x 2,5 RE | ||||
Keram (N)HXH-J FE180 E30-E60 0,6/1 kV n1 x 1,5 RE | ||||
Keram (N)HXH-J FE180 E30-E60 0,6/1 kV n1 x 2,5 RE | ||||
Keram (N)HXH-J FE180 E90 0,6/1 kV n2 x 1,5 RE | ||||
Keram (N)HXH-J FE180 E90 0,6/1 kV n3 x 2,5 RE | ||||
KLICK30 | Ceiling | X-P 17 B3 MX / X-P 20 B3 MX / Fire-rated Anchor* |
BETAflam® (N)HXH-J FE180 / E30–E60 S 0,6/1kV n1 x 1,5 RE | 4 |
BETAflam® (N)HXH-J FE180 / E30–E60 S 0,6/1kV n1 x 2,5 RE | ||||
EUCASAFE® (N)HXH FE 180 E30 - E60 0,6/1 kV n1 x 1,5 RE | ||||
EUCASAFE® (N)HXH FE 180 E90 0,6/1 kV n1 x 1,5 RE | ||||
EUCASAFE® (N)HXH FE 180 E90 0,6/1 kV n3 x 2,5 RE | ||||
Keram (N)HXH-J FE180 E90 0,6/1 kV n2 x 1,5 RE | ||||
Keram (N)HXH-J FE180 E90 0,6/1 kV n3 x 2,5 RE | ||||
Wall | Fire-rated Anchor* | Keram (N)HXH-J FE180 E90 0,6/1 kV n3 x 2,5 RE | 3 | |
Wall 4 | Fire-rated Anchor* | EUCASAFE® (N)HXH FE 180 E30 - E60 0,6/1 kV n1 x 1,5 RE | 3 | |
EUCASAFE® (N)HXH FE 180 E30 - E60 0,6/1 kV n1 x 2,5 RE | ||||
1 n ≤ 30 | ||||
2 n ≤ 24 | ||||
3 n ≤ 12 | ||||
4 Vertical mount – Installed with opening facing up |
E30 Fire Rating Data Cable Capacity | ||||
---|---|---|---|---|
Part Number | Mount | Fastener | Cable | kg/m** |
KLICK15 | Ceiling | X-P 17 B3 MX / X-P 20 B3 MX / Fire-rated Anchor* |
BETAflam® JE-H(St)HRH FE180 / E30–E90 n1 x 2 x 0,8 | 3 |
EUCASAFE® JE-H(St)H...Bd FE 180 E30 max. 225 V n2 x 2 x 0,8 | ||||
EUCASAFE® JE-H(St)H...Bd FE 180 E90 max. 225 V n2 x 2 x 0,8 | ||||
KLICK30 | Ceiling | X-P 17 B3 MX / X-P 20 B3 MX / Fire-rated Anchor* |
BETAflam® JE-H(St)HRH FE180 / E30–E90 n2 x 2 x 0,8 | 4 |
EUCASAFE® JE-H(St)H...Bd FE 180 E30 max. 225 V n2 x 2 x 0,8 | ||||
EUCASAFE® JE-H(St)H...Bd FE 180 E90 max. 225 V n2 x 2 x 0,8 | ||||
1 n ≤ 32 | ||||
2 n ≤ 52 |
E60 Fire Rating Power Cable Capacity | ||||
---|---|---|---|---|
Part Number | Mount | Fastener | Cable | kg/m** |
KLICK15 | Ceiling | X-P 17 B3 MX / X-P 20 B3 MX / Fire-rated Anchor* |
BETAflam® (N)HXH-J FE180 / E30–E60 S 0,6/1kV n1 x 1,5 RE | 3 |
BETAflam® (N)HXH-J FE180 / E90 0,6/1kV n1 x 1,5 RE | ||||
BETAflam® (N)HXH-J FE180 / E90 0,6/1kV n2 x 2,5 RE | ||||
EUCASAFE® (N)HXH FE 180 E30 - E60 0,6/1 kV n1 x 2,5 RE | ||||
EUCASAFE® (N)HXH FE 180 E90 0,6/1 kV n1 x 1,5 RE | ||||
Keram (N)HXH-J FE180 E30-E60 0,6/1 kV n1 x 1,5 RE | ||||
Keram (N)HXH-J FE180 E30-E60 0,6/1 kV n1 x 2,5 RE | ||||
Keram (N)HXH-J FE180 E90 0,6/1 kV n2 x 1,5 RE | ||||
Wall | Fire-rated Anchor* | EUCASAFE® (N)HXH FE 180 E30 - E60 0,6/1 kV n1 x 1,5 RE | 3 | |
Keram (N)HXH-J FE180 E30-E60 0,6/1 kV n1 x 1,5 RE | ||||
Keram (N)HXH-J FE180 E30-E60 0,6/1 kV n1 x 2,5 RE | ||||
Keram (N)HXH-J FE180 E90 0,6/1 kV n2 x 1,5 RE | ||||
Keram (N)HXH-J FE180 E90 0,6/1 kV n3 x 2,5 RE | ||||
KLICK30 | Ceiling | X-P 17 B3 MX / X-P 20 B3 MX / Fire-rated Anchor* |
BETAflam® (N)HXH-J FE180 / E30–E60 S 0,6/1kV n1 x 2,5 RE | 4 |
EUCASAFE® (N)HXH FE 180 E90 0,6/1 kV n3 x 2,5 RE | ||||
Keram (N)HXH-J FE180 E90 0,6/1 kV n2 x 1,5 RE | ||||
Keram (N)HXH-J FE180 E90 0,6/1 kV n3 x 2,5 RE | ||||
Wall 4 | Fire-rated Anchor* | EUCASAFE® (N)HXH FE 180 E30 - E60 0,6/1 kV n1 x 1,5 RE | 3 | |
1 n ≤ 30 | ||||
2 n ≤ 24 | ||||
3 n ≤ 12 | ||||
4 Vertical mount – Installed with opening facing up |
E60 Fire Rating Data Cable Capacity | ||||
---|---|---|---|---|
Part Number | Mount | Fastener | Cable | kg/m** |
KLICK15 | Ceiling | X-P 17 B3 MX / X-P 20 B3 MX / Fire-rated Anchor* |
BETAflam® JE-H(St)HRH FE180 / E30–E90 n1 x 2 x 0,8 | 3 |
EUCASAFE® JE-H(St)H...Bd FE 180 E90 max. 225 V n2 x 2 x 0,8 | ||||
KICK30 | Ceiling | X-P 17 B3 MX / X-P 20 B3 MX / Fire-rated Anchor* |
BETAflam® JE-H(St)HRH FE180 / E30–E90 n2 x 2 x 0,8 | 4 |
EUCASAFE® JE-H(St)H...Bd FE 180 E90 max. 225 V n2 x 2 x 0,8 | ||||
1 n ≤ 32 | ||||
2 n ≤ 52 |
E90 Fire Rating Power Cable Capacity | ||||
---|---|---|---|---|
Part Number | Mount | Fastener | Cable | kg/m** |
KLICK15 | Ceiling | X-P 17 B3 MX / X-P 20 B3 MX / Fire-rated Anchor* |
BETAflam® (N)HXH-J FE180 / E90 0,6/1kV n1 x 1,5 RE | 3 |
BETAflam® (N)HXH-J FE180 / E90 0,6/1kV n2 x 2,5 RE | ||||
Wall | Anchor | Keram (N)HXH-J FE180 E90 0,6/1 kV n3 x 2,5 RE | 3 | |
1 n ≤ 30 | ||||
2 n ≤ 24 | ||||
3 n ≤ 12 |
E90 Fire Rating Data Cable Capacity | ||||
---|---|---|---|---|
Part Number | Mount | Fastener | Cable | kg/m** |
KLICK15 | Ceiling | X-P 17 B3 MX / X-P 20 B3 MX / Fire-rated Anchor* | BETAflam® JE-H(St)HRH FE180 / E30–E90 n1 x 2 x 0,8 | 3 |
EUCASAFE® JE-H(St)H...Bd FE 180 E90 max. 225 V n2 x 2 x 0,8 | ||||
KLICK30 | Ceiling | X-P 17 B3 MX / X-P 20 B3 MX / Fire-rated Anchor* | BETAflam® JE-H(St)HRH FE180 / E30–E90 n2 x 2 x 0,8 | 4 |
EUCASAFE® JE-H(St)H...Bd FE 180 E90 max. 225 V n2 x 2 x 0,8 | ||||
1 n ≤ 32 | ||||
2 n ≤ 52 |
Leták
Návod k instalaci / list s pokyny
Případová studie
Certifications
DIN 4102-12 AbP P-MPA-E-24-004
English,German
DIN 4102-12



- Upozornění
- Produkty nVent musí být instalovány a používány pouze tak, jak je uvedeno v instrukčních listech a materiálech pro školení nVent. Instrukční listy jsou k dispozici na www.nvent.com a od vašeho zástupce zákaznického servisu nVent. Nesprávná instalace, zneužití, nesprávné použití nebo jiný nedostatek úplného dodržování pokynů a varování nVent může způsobit selhání produktu, poškození majetku, vážné zranění osob a smrt a/nebo zrušit vaši záruku.