Skip to main content
Please Select Your Country/Language Preferences

nVent ERIFLEX Power Meters and Software Hover to magnify image or click to enlarge

nVent ERIFLEX Power Meters & Software

The nVent ERIFLEX Network Analyzer is a compact and innovative instrument designed for precise measurement and recording of electrical parameters. It is particularly well-suited for energy consumption analysis and control.

Its quick and easy connection system makes it ideal for retrofitting existing switchboards or conducting energy audits. The analyzer is the perfect tool for establishing measurement points across a facility.

Communication is supported via an RS485 serial port using MODBUS RTU protocol (PM RS485 version) and an Ethernet port using MODBUS TCP protocol (PM Ethernet version).

Remote management is available through the free EriflexNET software. For Ethernet models, an integrated web interface allows full access and control from any PC connected to the network, offering a convenient and intuitive way to manage the device remotely. You can download the EriflexNET software from the Resources tab below.

Read more Read less
  • RoHS
  • CE
Print This Page
Need technical support or a quote? We're here to help.
Contact Us Where to Buy
Details

Features

Specifications

Mounting Cutout 3.58x3.58"
Frequency 45 - 65 Hz
Mounting Cutout 91x91mm
Current Measurement Range 500 A; 4000 A; 20000 A
Input Voltage 600 VAC
Complies With 2014/30/EU;2014/35/EU;EN 61010-1;EN 61010-2-030
Installation Indoor
IP Rating IP54;IP20
Frequency Accuracy ±0.1% of Reading ±1 Digit within 45–65 Hz Range
Voltage Accuracy ±0.2% of Reading within 10% FS to FS Range
Current Measurement Accuracy ±0.4% of Reading within 5% FS to FS Range
Operating Temperature -13 to 131 °F
Storage Temperature -13 to 167 °F
Operating Temperature -25 to 55 °C
Storage Temperature -25 to 75 °C
Humidity 80 % Max
Data Copied
Metric   |   Imperial
PMETHERNET PMRS485
Minimum voltage for FFT calculation 20/35 VAC (direct connection; multiplied by PT ratio when using PT)
Starting current (Ist) 3A for FSA 500A
25A for FSA 4000A
120A for FSA 20000A
Current Inputs Rogowski coil inputs
(3 coils, ordered separately)
Wiring Modes Compatible with both single-phase and three-phase systems
Active power/energy accuracy Class 0.5 per IEC/EN 61557-12
Reactive power/energy accuracy Class 2 per IEC/EN 61557-12
Digital Outputs Type: 2 x NPN, Passive Optoisolated
Max Values: 27 VDC - 27 mA
Digital Inputs Type: Optoisolated
Voltage Range: 80 - 265 VAC-DC
Terminal wire diameters Measuring Terminals: 2.5 mm2 / 14 AWG
I/O, AUX, RS485 terminals: 1.5 mm2 / 16 AWG

Diagrams

Application images Resources
Warning
nVent products shall be installed and used only as indicated in nVent's product instruction sheets and training materials. Instruction sheets are available at www.nvent.com and from your nVent customer service representative. Improper installation, misuse, misapplication or other failure to completely follow nVent's instructions and warnings may cause product malfunction, property damage, serious bodily injury and death and/or void your warranty.
Need technical support or a quote? We're here to help.
Contact Us Where to Buy